two CDUs, N+N · site water 20 °C → PG25 25 °C · live process
t = 00:00:00▶ Your turn: break it and watch what happens
The diagram above is a live model. Each button is a switch: press once to turn it off, press again to turn it back on.
Red = running / full load · outline = stopped / half load
Start with switch 1: turn CDU A off and watch CDU B pick up the whole load.
Steady-state forecast at the current settings · every unit state against every load
Rack load · 5 racks × 40 kW
Process
CDUs and time
Keys A and B stop or start a unit. Stop one and watch the other valve open to carry the whole load; stop both and the racks heat up until the switches throttle.
Model assumptions
Every number is computed, not scripted. Liquid is advected through the pipes as plug flow at its real velocity (drawing scale 40 px = 1 m), so a change at a valve takes real seconds to reach the racks. Dots move at the actual pipe velocity and are coloured by the local liquid temperature. Hover any pipe for flow, velocity, Reynolds number and transit time. Design data from the Design document, edition 3: 200 kW in 5 racks, site water 20 °C in and 28 °C out, DN80 branches, PG25 secondary at 302 L/min with a 10 K rise, two 345 kW liquid-to-liquid CDUs in N+N. Model assumptions, to be replaced by vendor data when they arrive: water ρ·cp 4.187 MJ/m³·K (1.163 kW per m³/h·K), PG25 ρ 1020 kg/m³ and cp 3.90 kJ/kg·K; schedule-40 pipe bores; each heat exchanger has an effective UA of kW/K, derived from the Vendor rating of 345 kW at a 4 K approach (read as site water 20 → 28 °C against PG25 34 → 24 °C, a log-mean difference of 4.93 K); primary valve Kvs 40 m³/h equal-percentage (R 50) with a 60 s actuator; secondary pumps 30 m head at full flow, 55 % wire-to-water; racks receive equal flow; switches throttle as their coolant passes 65 °C. The chip temperature is an estimate, because The vendor has not published thermal data: junction = hottest coolant in the rack + 20 K cold-plate rise + 15 K junction-to-case at 40 kW per rack and design flow, both scaled with the load, the convective 60 % of the cold-plate rise scaled with flow−0.8; it turns yellow at 85 °C and red at 100 °C. The traffic light applies one set of rules to the live state and to the forecast table; the forecast is a steady-state calculation (counter-flow effectiveness-NTU) at the current slider settings with the load spread evenly over the racks.