Liquid Cooling in Practice: What Happens When One CDU Fails
Stop a CDU yourself in our live 200 kW simulation and watch what happens.
Interactive simulation  ·  3 min read + play

Every liquid-cooling drawing shows two CDUs and the words "N+N redundancy". But what really happens in the seconds after one unit stops? Don't take our word for it. Break it yourself in the live model below.

▶ Live CDU simulation 200 kW · 5 racks · two CDUs in N+N · every number computed live
Open full screen ↗

01Three things to try

1

Switch CDU A off. The other unit opens its valve and carries the full 200 kW. Coolant supply jumps about 3 °C, then recovers in about two minutes.

2

Switch CDU B off too. Nothing removes heat any more. At full load the racks reach their throttling point in under a minute.

3

Switch both back on, then toggle the load. With two oversized units sharing the load, it returns 5–7 °C warmer than the design value, at about half the flow.

02What it means for your design

  • Size the margin for the failover, not for steady state. The 3 °C bump hits every rack at once.
  • Put CDU pumps and controls on UPS. You have seconds, not minutes.
  • Check the facility side in every mode. Ask whether the design return temperature is a hard limit.

The model uses published CDU ratings and engineering assumptions (heat-exchanger coefficient, valve and pump data). Open "Model assumptions" at the bottom of the simulation for details. Validate against vendor data for your own project.